亚洲国产日韩a在线播放-亚洲国产日韩a在线亚洲-亚洲国产日韩成人综合天堂-亚洲国产日韩女人aaaaaa毛片在线-亚洲国产日韩欧美-亚洲国产日韩欧美一区二区三区

當(dāng)前位置: 首頁 - 新聞資訊 > 常見問題

通風(fēng)管道安裝規(guī)范有哪些?

來源:http://www.euio.com.cn 日期:2020-03-17 發(fā)布人:admin

1、通風(fēng)管道水平安裝,水平度的允許偏差每m不應(yīng)大于3mm,總偏差不應(yīng)大于20mm;通風(fēng)管道垂直安裝,垂直度的允許偏差每m不應(yīng)大于2mm,總偏差不應(yīng)大于20mm。
1. For horizontal installation of ventilation pipes, the allowable deviation of levelness shall not be greater than 3m m per m, and the total deviation shall not be greater than 20mm; for vertical installation of ventilation pipes, the allowable deviation of verticality shall not be greater than 2mm per m, and the total deviation shall not be greater than 20mm.
2、管道吊架距法蘭距離不小于20mm。柔性短管長度為150~300mm.金屬軟管及非金屬軟管長度不得大于2m,并不用有死彎或塌凹。
2. The distance between pipe hanger and flange shall not be less than 20 mm. The length of flexible short pipe is 150-300 mm. The length of metal hose and non-metal hose shall not be more than 2 m, and there is no dead bend or collapse.
3、主通風(fēng)管道吊架距支管之間的距離應(yīng)不小于200mm。
3. The distance between the main ventilation pipe hanger and the branch pipe shall not be less than 200mm.
4、法蘭螺栓孔距低壓送風(fēng)不大于200mm,中壓送風(fēng)距離不大于100mm。5 ) 通風(fēng)管道彎頭處、三通處、閥門處、必須加吊架、管道長度超過15m,防晃支架不得少于一個。
4. The distance between the flange bolt hole and the low-pressure air supply shall not be greater than 200mm, and the distance between the middle pressure air supply shall not be greater than 100mm. 5) hangers must be added at the elbows, tees and valves of the ventilation pipes. The length of the pipes is more than 15m, and there shall be no less than one anti sway support.
6、通風(fēng)管道吊架距不保溫通風(fēng)管道邊緣為30mm,距保溫通風(fēng)管道保溫層邊緣距離為30mm。
6. The distance between the hanger of the ventilation pipe and the edge of the uninsulated ventilation pipe is 30mm, and the distance between the hanger and the edge of the insulation layer of the insulated ventilation pipe is 30mm.
7、通風(fēng)管道保溫應(yīng)平整,法蘭處必須單獨(dú)保溫,法蘭保溫材料應(yīng)與管道一致。通風(fēng)管道水平度為3‰,垂直度2‰,總體偏差均不大于20mm。
7. The thermal insulation of the ventilation pipe shall be flat, and the flange must be insulated separately, and the flange thermal insulation material shall be consistent with the pipe. The levelness and perpendicularity of ventilation pipes are 3 ‰ and 2 ‰, and the overall deviation is not more than 20 mm.
8、通風(fēng)管道與法蘭壓邊寬度應(yīng)為6~9mm,接觸嚴(yán)密并順直。
8. The width of air duct and flange flange flange shall be 6-9mm, with tight and straight contact.
9、玻璃鋼通風(fēng)管道法蘭連接,法蘭螺栓間距不大于120mm,法蘭間距均勻,法蘭平整,法蘭墊片厚度為3~5mm。
9. For flange connection of FRP ventilation pipe, the distance between flange bolts shall not be more than 120mm, the distance between flanges shall be uniform, the flange shall be flat, and the thickness of flange gasket shall be 3-5mm.
濟(jì)南通風(fēng)管道
10、玻璃鋼通風(fēng)管道長度超過20m時,應(yīng)加固定支架不得少于一個,玻璃鋼通風(fēng)管道長度超過20m時應(yīng)按設(shè)計要求加伸縮節(jié)。
10. When the length of FRP ventilation pipe exceeds 20 m, at least one fixed support shall be added. When the length of FRP ventilation pipe exceeds 20 m, expansion joint shall be added according to the design requirements.
11、通風(fēng)管道穿伸縮縫處應(yīng)采用軟連接,軟管長度為伸縮縫寬度加100mm。通風(fēng)管道保溫材料為巖棉時保溫應(yīng)采用鐵角包裝帶,打包帶間距為0.6~0.7m。通通風(fēng)管道規(guī)格在400mm以下的支吊架間距不大于4m,規(guī)格在400mm以上的通風(fēng)管道支吊架間距不大于3m.
11. Flexible connection shall be adopted at the place where the ventilation pipe passes through the expansion joint, and the length of the hose shall be the width of the expansion joint plus 100mm. When the thermal insulation material of the ventilation pipe is rock wool, the iron angle packing belt shall be used for thermal insulation, and the spacing of the packing belt shall be 0.6 ~ 0.7m. The distance between the supports and hangers of the ventilation pipe with the specification less than 400mm shall not be more than 4m, and the distance between the supports and hangers of the ventilation pipe with the specification more than 400mm shall not be more than 3m
13、通風(fēng)管道垂直安裝,支架間距不大于4m,玻璃鋼管不大于3m。
13. The ventilation pipe shall be installed vertically, and the support spacing shall not be more than 4m, and the glass steel pipe shall not be more than 3m.
14、排通風(fēng)管道與屋面風(fēng)機(jī)連接應(yīng)墊6mm的橡膠墊,鍍鋅螺栓應(yīng)加平光墊和彈簧墊圈。
14. 6mm rubber pad shall be used for the connection between exhaust ventilation pipe and roof fan, and flat mat and spring washer shall be added for galvanized bolt.
15、室外鐵皮通風(fēng)管道保溫應(yīng)平整、光滑、咬口不小于20~25mm。
15. The insulation of outdoor iron sheet ventilation pipe shall be flat and smooth, and the undercut shall not be less than 20 ~ 25mm.
上一篇:性能良好的離心風(fēng)機(jī)故障維修!
下一篇:暖通工程風(fēng)管安裝施工控制!

產(chǎn)品

  • 廚房排煙
  • 廚房排煙
  • 軸流風(fēng)機(jī)
  • 不銹鋼制品

本站圖片均由網(wǎng)站所有方提供,部分圖片來源于網(wǎng)絡(luò),如有任何疑問請及時與我們聯(lián)系,未經(jīng)溝通本站不承擔(dān)相關(guān)法律責(zé)任!

主站蜘蛛池模板: 视频1区| 91色综合| 成年视频xxxxxx在线| 97在线公开视频| 一级一级毛片免费播放| 亚洲成人网在线观看| 日日添天天做天天爱| 日韩伦理一区| 女性一级全黄生活片| 精精国产www视频在线观看免费| 草逼综合| 伊人免费网| 午夜欧美精品久久久久久久久| 日韩中文字幕高清在线专区| 久久亚洲国产精品五月天| 国产精品亚洲欧美| 99爱视频精品免视看| 亚洲视频免费观看| 视频在线一区二区| 看毛片网| 国产亚洲欧美在在线人成| 波多野结衣在线观看3人| 亚洲精品一级一区二区三区| 日日摸夜夜爽人人添| 久久美女免费视频| 国产伦精品一区二区三区在线观看| 110139日韩欧美| 性欧美疯狂猛交69hd| 欧美久久精品| 国产香蕉在线视频一级毛片| 99热久久精里都是精品66| 亚洲va欧美va国产va天堂| 欧美国产成人精品一区二区三区| 久草高清视频| 国产国语videosex| 亚洲专区一路线二| 色婷婷狠狠五月综合天色拍| 免费看一区二区三区| 国产精品久久久久久久伊一| 377p欧洲最大胆艺术| 色综合综合色|